The MM90 HP unit medical manifold is intended for use in hospital pipeline systems as medical gas source. Together with MM90, always use an alarm providing all alarms according to standard (like gas alarm). As 2nd stage is recommended to use a stabilizer. The manifold will deliver gas from the operating bank to the manifold pressure regulator until the cylinders are exhausted. At that point the supply will switch to the reserve bank and the exhausted bank can be replenished. The object gives uninterrupted gas supply.
Gas Alarm is a standard accessory. The gas alarm gives a visual and audible indication. It surveils and the alarm sounds when the following happens:
1. Change operation side
2. Leaking on reserve side
3. High operation pressure
4. Low operation pressure
The gas alarm is able to communicate with other equipment through relays.
MM90 INCLUDES THE FOLLOWING COMPONENTS: MM90 HP unit Manifold, Gas alarm, Purge valves, HP filters
FOR A COMPLETE MM90 HP UNIT MANIFOLD ADD:
Collecting pipe set (high pressure valves, and non-return valves / high pressure components)
Cylinder retaining brackets (included in gas cylinder collecting pipe set)
High pressure hoses with safety wire
Plug for close collecting pipeline
Gas name sign
Stabilizer
03 | Product Information
Product Information
Item No.
Description
0732314
Denomination: MM90 – HP unit 2×1
Gas: O2
PRV: Standard
Signalization: Alarm TMA6703
0732315
Denomination: MM90 – HP unit 2×1
Gas: Air
PRV: Standard
Signalization: Alarm TMA6703
0732316
Denomination: MM90 – HP unit 2×1
Gas: N2O, CO2
PRV: Standard
Signalization: Alarm TMA6703
0732320
Denomination: MM90 – HP unit 2×1
Gas: O2, Air
PRV: With pull-ring
Signalization: Alarm TMA9705
0732321
Denomination: MM90 – HP unit 2×1
Gas: N2O, CO2
PRV: With pull-ring
Signalization: Alarm TMA9705
0727327*
Denomination: MM90 – HP unit 2×1
Gas: O2, N2O, Air, CO2, N2
PRV: Standard
*basic version without electric sensors
0732314
Denomination: MM90 – HP unit 2×1
Gas: O2
PRV: Standard
Signalization: Alarm TMA6703
0732315
Denomination: MM90 – HP unit 2×1
Gas: Air
PRV: Standard
Signalization: Alarm TMA6703
0732316
Denomination: MM90 – HP unit 2×1
Gas: N2O, CO2
PRV: Standard
Signalization: Alarm TMA6703
0732320
Denomination: MM90 – HP unit 2×1
Gas: O2, Air
PRV: With pull-ring
Signalization: Alarm TMA9705
0732321
Denomination: MM90 – HP unit 2×1
Gas: N2O, CO2
PRV: With pull-ring
Signalization: Alarm TMA9705
0727327*
Denomination: MM90 – HP unit 2×1
Gas: O2, N2O, Air, CO2, N2
PRV: Standard
*basic version without electric sensors
Regional information available in your language at
Complies with Medical Devices Directive 93/42/EEC
Complies with EN ISO 7396-1 (Central Gas Supply Systems)
Complies with EN 60601-1-2 (Electromagnetic compatibility)
present SIS HB 370 and HTM 02-01
Gases:
O2, Air, N2, N2O, CO2 (all medical gases)
Nominal flow:
90 m3/h
Inlet nominal pressure:
200 bar (20 000 kPa)
Outlet nominal pressure:
9 bar (setting range 9–15 bar)
Inlet connection:
W21,8×1/14"M
Outlet connection:
G3/4"F + soldering piece pipe ø 22 mm
Intermediate pressure relieve valve:
16 bar
Pressure relieve valve pipe dimension:
ø 10 mm
Purge valves connection:
W21,8×1/14"M + soldering piece pipe ø 10mm
Regulatory status:
Complies with Medical Devices Directive 93/42/EEC
Complies with EN ISO 7396-1 (Central Gas Supply Systems)
Complies with EN 60601-1-2 (Electromagnetic compatibility)
present SIS HB 370 and HTM 02-01
We use cookies on our website to give you the most relevant experience by remembering your preferences and repeat visits. By clicking “Accept”, you consent to the use of ALL the cookies.
This website uses cookies to improve your experience while you navigate through the website. Out of these, the cookies that are categorized as necessary are stored on your browser as they are essential for the working of basic functionalities of the website. We also use third-party cookies that help us analyze and understand how you use this website. These cookies will be stored in your browser only with your consent. You also have the option to opt-out of these cookies. But opting out of some of these cookies may affect your browsing experience.